====== omron.v7 ======
Частотный преобразователь Omron V7.
Используемый протокол - MODBUS.
http://www.omronkft.hu/nostree/pdfs/inverter/cimr-v7az/v7az.pdf
plugin.peripherial:
module.omron1:
portnum: 2
netaddr: 1
enable: on
type: omron.v7
===== Теги =====
Reg0001
Reg0002
Reg0020
Reg0021
Reg0022
Reg0023
Reg0024
Reg0027
Reg0028
Reg0029
Reg002A
SYSTEM.ErrorCount
SYSTEM.ErrorFlag
SYSTEM.NetAddr
SYSTEM.Port
SYSTEM.TimePeriod
SYSTEM.UpdateDate
SYSTEM.UpdateTime
==== Регистры ====
* **Reg0001**
* 0 Run Command - 1: Run, 0: Stop
* 1 Reverse Run Command 1: Reverse run 0: Forward run
* 2 External fault 1: Fault (EFO)
* 3 Fault Reset Command 1: Reset Command
* 4 Multi-function input reference 1 (Function selected by n050)
* 5 Multi-function input reference 2 (Function selected by n051)
* 6 Multi-function input reference 3 (Function selected by n052)
* 7 Multi-function input reference 4 (Function selected by n053)
* 8 Multi-function input reference 5 (Function selected by n054)
* 9 Multi-function input reference 6 (Function selected by n055)
* A Multi-function input reference 7 (Function selected by n056)
* B-F (Not used)
* **Reg0002** - Frequency reference (unit: n152)
* **Reg0020** - Status signal
* 0 Run Command 1: Run 0: Stop
* 1 Reverse Run Command 1: Reverse run 0: Forward run
* 2 Inverter operation ready 1: Ready 0: Not ready
* 3 Fault 1: Fault
* 4 Data setting error 1: Error
* 5 Multi-function output 1 (1: MA ON 0: MA OFF)
* 6 Multi-function output 2 (1: P1 ON 0: P1 OFF)
* 7 Multi-function output 3 (1: P2 ON 0: P2 OFF)
* 8-F (Not used)
* **Reg0021** - Fault description
* 0 Overcurrent (OC)
* 1 Overvoltage (OV)
* 2 Inverter overload (OL2)
* 3 Inverter overheat (OH)
* 4 (Not used)
* 5 (Not used)
* 6 PID feedback loss (FbL)
* 7 External fault (EF, EFO), Emergency stop (STP)
* 8 Hardware fault (FXX)
* 9 Motor overload (OL1)
* A Overtorque detection (OL3)
* B Undertorque detection (UL3)
* C Power loss (UV1)
* D Control power fault (UV2)
* E MEMOBUS communications timeover (CE)
* F Operator connection fault (OPR
* **Reg0022** - Data link status
* 0 Data write in
* 1 (Not used)
* 2 (Not used)
* 3 Upper/lower limit fault
* 4 Consistency fault
* 5-F (Not used)
* **Reg0023** - Frequency reference (unit: n152)
* **Reg0024** - Output frequency (unit: n152)
* **Reg0027** - Output current (10/1 A)
* **Reg0028** - Output voltage reference (1/1 V)
* **Reg0029** - Fault description
* 0 (Not used)
* 1 (Not used)
* 2 Input open phase (PF)
* 3 Output open phase (LF)
* 4-F (Not used)
* **Reg002A** - Alarm description
* 0 Operation function stop (STP)
* 1 Sequence error (SER)
* 2 Simultaneous FWD/REV Run Commands (EF)
* 3 External Baseblock (BB)
* 4 Overtorque detection (OL3)
* 5 Cooling fan overheat (OH)
* 6 Main circuit overvoltage (OV)
* 7 Main circuit undervoltage (UV)
* 8 Cooling fan fault (FAN)
* 9 Communications fault (CE)
* A Option card communications error (BUS)
* B Undertorque (UL3)
* C Inverter overheat alert (OH3)
* D PID feedback loss (FBL)
* E Emergency stop (STP)
* F Communications waiting (CAL)