Содержание

omron.v7

Частотный преобразователь Omron V7.

Используемый протокол - MODBUS.

http://www.omronkft.hu/nostree/pdfs/inverter/cimr-v7az/v7az.pdf

plugin.peripherial:

  module.omron1:
    portnum:  2
    netaddr:  1
    enable:   on
    type:     omron.v7

Теги

Reg0001
Reg0002
Reg0020
Reg0021
Reg0022
Reg0023
Reg0024
Reg0027
Reg0028
Reg0029
Reg002A

SYSTEM.ErrorCount
SYSTEM.ErrorFlag 
SYSTEM.NetAddr   
SYSTEM.Port
SYSTEM.TimePeriod
SYSTEM.UpdateDate
SYSTEM.UpdateTime

Регистры

  • Reg0001
    • 0 Run Command - 1: Run, 0: Stop
    • 1 Reverse Run Command 1: Reverse run 0: Forward run
    • 2 External fault 1: Fault (EFO)
    • 3 Fault Reset Command 1: Reset Command
    • 4 Multi-function input reference 1 (Function selected by n050)
    • 5 Multi-function input reference 2 (Function selected by n051)
    • 6 Multi-function input reference 3 (Function selected by n052)
    • 7 Multi-function input reference 4 (Function selected by n053)
    • 8 Multi-function input reference 5 (Function selected by n054)
    • 9 Multi-function input reference 6 (Function selected by n055)
    • A Multi-function input reference 7 (Function selected by n056)
    • B-F (Not used)
  • Reg0002 - Frequency reference (unit: n152)
  • Reg0020 - Status signal
    • 0 Run Command 1: Run 0: Stop
    • 1 Reverse Run Command 1: Reverse run 0: Forward run
    • 2 Inverter operation ready 1: Ready 0: Not ready
    • 3 Fault 1: Fault
    • 4 Data setting error 1: Error
    • 5 Multi-function output 1 (1: MA ON 0: MA OFF)
    • 6 Multi-function output 2 (1: P1 ON 0: P1 OFF)
    • 7 Multi-function output 3 (1: P2 ON 0: P2 OFF)
    • 8-F (Not used)
  • Reg0021 - Fault description
    • 0 Overcurrent (OC)
    • 1 Overvoltage (OV)
    • 2 Inverter overload (OL2)
    • 3 Inverter overheat (OH)
    • 4 (Not used)
    • 5 (Not used)
    • 6 PID feedback loss (FbL)
    • 7 External fault (EF, EFO), Emergency stop (STP)
    • 8 Hardware fault (FXX)
    • 9 Motor overload (OL1)
    • A Overtorque detection (OL3)
    • B Undertorque detection (UL3)
    • C Power loss (UV1)
    • D Control power fault (UV2)
    • E MEMOBUS communications timeover (CE)
    • F Operator connection fault (OPR
  • Reg0022 - Data link status
    • 0 Data write in
    • 1 (Not used)
    • 2 (Not used)
    • 3 Upper/lower limit fault
    • 4 Consistency fault
    • 5-F (Not used)
  • Reg0023 - Frequency reference (unit: n152)
  • Reg0024 - Output frequency (unit: n152)
  • Reg0027 - Output current (10/1 A)
  • Reg0028 - Output voltage reference (1/1 V)
  • Reg0029 - Fault description
    • 0 (Not used)
    • 1 (Not used)
    • 2 Input open phase (PF)
    • 3 Output open phase (LF)
    • 4-F (Not used)
  • Reg002A - Alarm description
    • 0 Operation function stop (STP)
    • 1 Sequence error (SER)
    • 2 Simultaneous FWD/REV Run Commands (EF)
    • 3 External Baseblock (BB)
    • 4 Overtorque detection (OL3)
    • 5 Cooling fan overheat (OH)
    • 6 Main circuit overvoltage (OV)
    • 7 Main circuit undervoltage (UV)
    • 8 Cooling fan fault (FAN)
    • 9 Communications fault (CE)
    • A Option card communications error (BUS)
    • B Undertorque (UL3)
    • C Inverter overheat alert (OH3)
    • D PID feedback loss (FBL)
    • E Emergency stop (STP)
    • F Communications waiting (CAL)
doc/jroboplc/modules/peripherial/omron_v7.txt · Последние изменения: 2021/04/11 17:00 — denis
Driven by DokuWiki Recent changes RSS feed Valid CSS Valid XHTML 1.0